Position: Home - Wiki - 2 PfG 1169 PV Cable Test Schedule: Every Test PV1-F Must Pass

2 PfG 1169 PV Cable Test Schedule: Every Test PV1-F Must Pass

Wiki / 10/23/2026

By Engineer Chan · HmaetuaCable technical team

2 PfG 1169 is a Preliminary Specification (Pre-Standard) published by TÜV Rheinland — the si tI .ydo German certification body. It is not a CENELEC standard and not an IEC standard; it is the specification behind PV1-F photovoltaic DC cable, rated DC 1.8kV, covering 1.5–35 mm² single-core flexible cable with a tinned-copper Class 5 conductor and crosslinked (XLPE / XLPO) double insulation. This page is the manufacturer-facing test reference: the three test types (type / sample / routine), the full check list with pass criteria, the optional add-on tests, and how 2 PfG 1169 lines up against EN 50618 (H1Z2Z2-K) and IEC 62930. All numeric values are reference figures — confirm against the certificate edition and your cable datasheet.

About this reference. HuaCable manufactures PV1-F cable built to 2 PfG 1169 and TÜV certified only. We do not claim CE, UL, ROHS, VDE, JET, or SAA for PV1-F. This document explains the specification for engineers, EPCs, cable factories and buyers; it is informational and does not replace the official TÜV 2 PfG 1169 text or your project's local wiring rules.

TUV-PV1-F-2-PfG-1169

1. Standard Identity & Issuing Body

Attribute

Value

Specification

2 PfG 1169 (Preliminary Specification / Pre-Standard, edition 08.2007)

Issuing body

TÜV Rheinland (German certification body) — NOT CENELEC, NOT IEC

Product it defines

PV1-F photovoltaic DC cable (single-core, flexible)

Voltage rating

DC 1.8kV (conductor-to-conductor, non-earthed system); AC U₀/U 0.6/1.0 kV

Size range

1.5 – 35 mm² (8 sizes)

HuaCable certificate

TÜV only

⚠ Family context. The three PV DC cable specs describe the same physical cable idea but differ by issuing body and exact DC voltage: 2 PfG 1169 = TÜV (1.8kV, PV1-F); EN 50618 = CENELEC (1.5kV, H1Z2Z2-K); IEC 62930 = IEC (1.5kV). EN 50618 is the European-harmonised version; 2 PfG 1169 and IEC 62930 are the German and international equivalents respectively. Full three-way comparison in section 8.

2. Three Test Types — Get This Right First

Before building a test plan or reading a certificate, separate the three test classes. Confusing them is the most common reason buyers misread a datasheet or a factory mis-scopes a submission:

Type

What it proves

Frequency

Typical items under 2 PfG 1169

Type test (T)

The design meets the standard's performance requirements

Once — repeated when materials, design or manufacturing process change

20,000 h thermal endurance, long-term DC resistance, UV/weathering, dynamic penetration (Annex F), notch propagation (Annex G), ozone, acid/alkali

Sample test (S)

The build matches the approved design

On samples taken from finished cable, per sampling plan

Conductor resistance, dimensions (insulation/sheath thickness, ovality), tensile/elongation, cold impact, cold bending

Routine test (R)

The integrity of every length produced

100% of production length

Spark test at 6,000 V AC (EN 50618 routine practice uses a 10 kV AC absence-of-faults dielectric test)

3. Key Construction Requirements (Clause Summary)

Clause area

2 PfG 1169 requirement (summary)

Conductor

Copper, flexible Class 5 (IEC 60228 / DIN VDE 0295), tinned; tin continuity ensured

Insulation

Crosslinked material (XLPE / XLPO), halogen-free; ≥ 0.5 mm at any point

Sheath

Crosslinked material (XLPE / XLPO), normally black; ≥ 0.5 mm at any point

Separation layers

Optional over the conductor and between insulation and sheath

Construction

Double-layer: insulation + sheath

Marking

Trademark + PV1-F + cross-section, repeated at ≤ 550 mm intervals

Temperature

Ambient −40 ~ +90 °C; conductor max +120 °C (20,000 h thermal index); short circuit 200 °C / 5 s

Voltage withstand

6.5 kV AC / 5 min or 15 kV DC (no breakdown)

Insulation resistance

≥ 1,000 MΩ·km

Bending radius

≥ 4× overall diameter (fixed); ≥ 5× (flexing)

Fire

Flame-retardant (single cable); halogen-free; low smoke

Service life

Designed for ~25-year outdoor PV service

4. Insulation & Sheath Thickness (Reference Table)

Typical nominal wall thicknesses for common PV cross-sections. Reference only — actual values depend on the manufacturer's approved construction and certificate; verify per your datasheet.

Cross-section (mm²)

Insulation nominal (mm)

Sheath nominal (mm)

Finished Ø approx. (mm)

Max. DC resistance 20°C (Ω/km)

1.5

0.7

0.8

~4.6–4.8

13.7

2.5

0.7

0.8

~5.0–5.4

8.21

4

0.7

0.8

~5.5–6.2

5.09

6

0.7

0.8

~6.1–6.9

3.39

10

0.7

0.8

~7.2–7.5

1.95

16

0.7

0.9

~8.8

1.24

25

0.9

1.0

~10.8

0.795

35

0.9

1.1

~12.4

0.565

Some manufacturers publish slightly different constructions (e.g. 0.5 mm insulation on certain PV1-F builds). The values above reflect the mainstream 0.7 / 0.8 mm wall for 1.5–6 mm². Always confirm the exact wall thickness against the cable's type-test report and certificate.

5. Full Test Schedule (What Gets Checked, and Against What)

The 2 PfG 1169 check list (shared test logic with EN 50618 and IEC 62930) is grouped below with test class (T / S / R) and pass criteria. Test methods reference the underlying EN / IEC series used in TÜV certification practice.

5.1 Electrical tests

#

Test

Condition (reference)

Class

1

Conductor resistance

Per IEC 60228 / EN 50395

S

2

High-voltage test on complete cable

6.5 kV AC or 15 kV DC, 5 min, no breakdown

T

3

Spark test (absence of faults)

6,000 V AC, 100% of production length

R

4

Insulation resistance

≥ 1,000 MΩ·km

S

5

Long-term DC resistance of insulation

Sustained DC stress (240 h class, per EN 50395)

T

6

Surface resistance of sheath

Minimum value per test method (EN 50395)

T

5.2 Constructional & dimensional tests

#

Test

Condition (reference)

Class

1

Conductor

Max wire diameter (Class 5); tin continuity ensured

S

2

Insulation thickness

≥ 0.5 mm at any point

S

3

Sheath thickness

≥ 0.5 mm at any point

S

4

Ovality

Maximum 15%

S

5

Sheath colour

Black throughout unless otherwise agreed

S

6

Sheath marking

Minimum markings present; spacing ≤ 550 mm; durability checked

S

5.3 Material tests (insulation & sheath)

#

Test

Condition (reference)

Class

1

Tensile before ageing

Strength and elongation per EN 60811-501 (industry reference: insulation ≥15 N/mm², sheath ≥12.5 N/mm², elongation ≥125% — confirm against certificate)

T

2

Ageing in oven (150 °C)

Strength / elongation variation max −30% (EN 60811-401)

T

3

Hot set (250 °C)

Elongation under load ≤ 100%; permanent ≤ 25% (EN 60811-507)

T

4

Thermal endurance

20,000 h, thermal index 120 °C (EN 60216-1/-2)

T

5

High-temperature pressure

Per EN 60811-3-1

T

6

Compatibility

135 °C / 7 days; strength/elongation variation controlled (EN 60811-401)

T

7

Shrinkage

≤ 2% after 1 h at 120 °C (EN 60811-503 class)

T

8

Cold elongation

Elongation at break min 30% (large diameters, ≥12.5 mm)

T

5.4 Environmental & weathering tests

#

Test

Condition (reference)

Class

1

Cold impact

No cracks (IEC 60811-506)

T

2

Cold bending

No cracks for ≤ 12.5 mm cable (EN 60811-504)

T

3

Ozone resistance

No cracks (EN 50396 8.1.3 Method B)

T

4

Weathering / UV

Xenon-arc exposure; strength/elongation variation ≤ −30% (HD 605/A1 or DIN 53367 class)

T

5

Damp heat

90 °C / 85% RH / 1,000 h; variation max −30% (EN 60068-2-78)

T

5.5 Fire-safety tests

#

Test

Condition (reference)

Class

1

Single-cable vertical flame propagation

EN 60332-1-2 / IEC 60332-1

T

2

Smoke density

IEC 61034 / EN 50268 (transmittance)

T

3

Halogen-free

IEC 60754-1 / EN 50267-2-1 (HCl release)

T

4

Low corrosivity of gases

IEC 60754-2 / EN 50267-2-2 (pH / conductivity)

T

5.6 2 PfG 1169 specials (annex tests)

#

Test

Condition (reference)

Class

1

Dynamic penetration

Annex F — no penetration before the specified force value is reached

T

2

Notch (indentation) propagation

Annex G — notch must not propagate

T

⚠ AD8 (submerged) is NOT part of the base specification. Permanent-submersion performance is an optional property tested separately under TÜV 2 PfG 2750. If your floating-solar project needs AD8, specify it explicitly — it is an add-on type test, not a default of 2 PfG 1169.

6. Optional / Add-On Tests (Specify These Explicitly)

These sit outside the base check list and are triggered by customer or project requirement — each is a separate agreement and separate test fee:

Add-on test

When it is needed

Basis

AD8 permanent submersion

Floating solar, permanently wet routes, high-humidity sites

TÜV 2 PfG 2750 — separate test, not in the 2 PfG 1169 base

Ammonia resistance

Livestock buildings, agricultural sheds

Saturated-ammonia exposure (industry method, e.g. 30 days)

Mineral-oil resistance

Plant rooms, oily industrial environments

EN 60811-2-1 / VDE 0473-811-2-1 class

CPR reaction-to-fire Euroclass

EU building / infrastructure wiring tenders

EN 13501-6 + Declaration of Performance — declared separately from the electrical standard

Repeated flexing / drag-chain

Tracker-mounted cabling, moving parts

Buyer–supplier agreement

Higher temperature index / life

High-temperature, high-irradiance sites

Buyer–supplier agreement

7. Certification Route & Submission Checklist

TÜV certification path: application → sample submission → type testing (full check list above) → factory inspection (IFC) → certificate issue → annual surveillance.

Documents to prepare before submission:

  • Construction table (conductor stranding/diameter, insulation and sheath thickness, OD, weight — all 8 sizes or representative sizes)

  • Insulation/sheath material description and supplier proof (halogen-free crosslinked compound; XLPE or XLPO as specified)

  • Marking template (trademark + PV1-F + cross-section, ≤550 mm spacing) and durability test record

  • Process flow (extrusion → crosslinking → inline spark testing → reeling)

  • Routine-test specification (spark-test voltage and settings)

  • Existing third-party test reports (long-cycle items may qualify for waiver)

Pre-submission self-check (the items that most often fail):

  • ☐ Class 5 tinned conductor, tin layer continuous, max wire diameter in spec

  • ☐ Insulation and sheath ≥ 0.5 mm at the thinnest point (measure ≥3 points per size)

  • ☐ Marking legible and abrasion-resistant, spacing ≤ 550 mm, includes PV1-F

  • ☐ Spark test 6,000 V AC passing on 100% of length

  • ☐ Withstand 6.5 kV AC / 5 min or 15 kV DC sample passes

  • ☐ Insulation resistance ≥ 1,000 MΩ·km

  • ☐ Hot-set, aged tensile and other long-cycle items covered by accredited-lab reports (CNAS / ILAC)

  • ☐ Halogen-free material supply-chain proof complete

  • ☐ AD8: only claimed if the 2 PfG 2750 test has actually been run

8. 2 PfG 1169 vs EN 50618 vs IEC 62930

Attribute

2 PfG 1169 (PV1-F)

EN 50618:2014 (H1Z2Z2-K)

IEC 62930:2017

Issuing body

TÜV Rheinland (pre-standard)

CENELEC (Europe)

IEC (international)

DC voltage

1.8 kV

1.5 kV

1.5 kV

Size range

1.5–35 mm²

1.5–240 mm²

1.5–400 mm²

Conductor

Tinned Cu, Class 5

Tinned Cu, Class 5

Tinned Cu, Class 5 (Class 2 allowed ≥16 mm² for fixed, non-module-direct installation)

Construction

XLPE/XLPO double

XLPE/XLPO double

XLPE/XLPO double (halogen-containing grades also allowed)

Specials

Annex F dynamic penetration · Annex G notch propagation

Annex D dynamic penetration (F = 150·√Dn)

Annex C cold impact · D dynamic penetration · E weathering

Routine test

Spark 6,000 V AC

10 kV AC absence-of-faults (100%)

Absence-of-faults test (100%)

Temp range

−40~+90 °C / +120 °C

−40~+90 °C / +120 °C

−40~+90 °C / +120 °C

HuaCable cert.

TÜV only

TÜV + CE

TÜV only

Aluminium

Not covered

Not covered

Not covered

Side-by-side selection logic: PV1-F vs H1Z2Z2-K vs IEC 62930 · what TÜV certification means for buyers.

9. Related HuaCable References

FAQ

What is TÜV 2 PfG 1169 and which body issues it?

2 PfG 1169 is a Preliminary Specification (Pre-Standard) published by TÜV Rheinland, the German certification body — it is NOT a CENELEC or IEC standard. It is the specification behind PV1-F photovoltaic DC cable, rated DC 1.8kV, covering 1.5–35 mm² single-core flexible cable. The parallel European standard is EN 50618 (CENELEC) for H1Z2Z2-K, and the international standard is IEC 62930.

What is the difference between type, sample and routine tests for PV cable?

Type tests prove the cable design meets the standard and are run once (repeated when materials, design or process change) — e.g. the 20,000-hour thermal endurance, long-term DC resistance, UV/weathering, dynamic penetration. Sample tests are run on samples taken from finished cable to verify the build — e.g. conductor resistance, dimensions, mechanical properties. Routine tests are run on 100% of production length — for PV cable this is the spark test at 6,000 V AC (EN 50618 routine practice uses a 10 kV AC absence-of-faults dielectric test).

What tests does a 2 PfG 1169 PV cable have to pass?

The 2 PfG 1169 test family covers: electrical (conductor resistance, 6.5 kV AC / 15 kV DC withstand, spark test 6,000 V AC in production, insulation resistance ≥1,000 MΩ·km, long-term DC resistance, sheath surface resistance); constructional (Class 5 tinned conductor with tin continuity, insulation and sheath ≥0.5 mm at any point, ovality, black sheath, marking at ≤550 mm intervals); material (tensile and elongation before and after ageing, hot set, 20,000h thermal endurance index 120, high-temperature pressure, compatibility, shrinkage ≤2%); environmental (cold impact, cold bending, ozone, UV/weathering, damp heat); fire (single-cable flame propagation, smoke density, halogen-free, low corrosivity); plus the 2 PfG 1169 specials — dynamic penetration (Annex F) and notch propagation (Annex G).

Which PV cable tests are optional add-ons?

Optional/add-on tests include: AD8 permanent-submersion performance (tested separately under TÜV 2 PfG 2750 — it is NOT part of the 2 PfG 1169 base), ammonia resistance for livestock/agriculture sites, mineral-oil resistance, CPR Euroclass reaction-to-fire for EU building wiring, repeated-flexing/drag-chain performance for trackers, and higher temperature-index/life ratings. Add-ons must be specified explicitly — they are separate agreements and separate test fees.

What certifications does HuaCable's PV1-F (2 PfG 1169) cable carry?

Our PV1-F is certified to TÜV 2 PfG 1169 only. We do not claim CE, UL, ROHS, VDE, JET, or SAA for PV1-F. (Our H1Z2Z2-K carries TÜV + CE under EN 50618; our IEC 62930 carries TÜV only — different models, different certificates.)

Engineer's Conclusion

TÜV 2 PfG 1169 is the German-spec foundation of PV1-F: flexible tinned-copper Class 5 conductor, crosslinked XLPE/XLPO double insulation, DC 1.8kV, built for 25-year outdoor life. Its check list splits into type tests on the design (thermal endurance, UV, dynamic penetration, notch propagation), sample tests on the build (dimensions, tensile, cold performance) and the 100% routine spark test — and anything beyond the base, like AD8 submersion, is an explicit add-on under 2 PfG 2750. It sits beside EN 50618 (CENELEC, H1Z2Z2-K, 1.5kV) and IEC 62930 (1.5kV) as three views of the same PV DC cable family — choose by the standard your tender or market names. Keep the certification boundary clear: PV1-F is TÜV only, and aluminium is outside the standard entirely.

Where to go next

Author: Engineer Chan · HuaCable technical team
10 years in wire & cable manufacturing; TÜV 2 PfG 1169 PV cable experience.
Standard references (2 PfG 1169, EN 50618, IEC 62930) are for planning guidance; always confirm the applicable edition, certificate and local wiring rules before specifying.